Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100106 E02 II B 2 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-13 |
Current Penalty |
1282.8 |
Initial Penalty |
2138.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: a) For the shop area, as observed on or about 10/20/2016, 125 gallons of category 2 and category 4 flammable liquids were located inside the shop in 55 gallon drums and a 30 gallon drum. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100106 E06 II |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-08 |
Current Penalty |
1282.8 |
Initial Penalty |
2138.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container: a) For the shop location, as observed on or about 10/25/2016, 55 gallon drums of non-chlorinated brake cleaner, a category 2 flammable liquid, were dispensed into aerosol cans without bonding the can to a metallic nozzle on the 55 gallon drum. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2016-12-01 |
Current Penalty |
1282.8 |
Initial Penalty |
2138.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) For the shop location, as observed on or about 10/20/2016, employees used a corrosive called Purple Power cleaner/degreaser to clean off vehicles. Suitable eyewash station/s were not present. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100038 B |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.38(b): An emergency action plan was not in writing, kept in the workplace, and available to employees for review: a) For the shop location, as observed on or about 10/20/2016, an emergency action plan was not in writing and available for employees to review. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100039 B |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.39(b): A fire prevention plan was not in writing, kept in the workplace, and made available to employees for review. a) For the shop location, as observed on or about 10/20/2016, a written fire prevention program was not available. |
|
Citation ID |
02003 |
Citaton Type |
Other |
Standard Cited |
19100106 D06 III |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
4 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(d)(6)(iii): The storage area was not graded in a manner to divert possible spills away from buildings or other exposures or was not surrounded by a curb at least 6 inches high; and/or provisions were not made for draining of accumulations of ground or rain water or spills of flammable liquids; and/or drains did not terminate at a safe location; and/or drains were not accessible to operation under fire conditions as required: a) For the storage area of gasoline and diesel adjacent to the building exterior wall, as observed on or about 10/20/2016, the storage area was not graded to divert spills away from buildings and was not surrounded by a curb at least 6 inches high; and/or provisions were not made for draining of accumulations of ground or rain water or spills of flammable liquids; and/or drains did not terminate at a safe location; and/or drains were not accessible to operation under fire conditions as required. Tanks were also not spaced 3 feet from each other and were not accessible to operation under fire conditions; rather, were located adjacent to one another. Alarms were also not in place for overfilling, and overfilling prevention was not in place. |
|
Citation ID |
02004 |
Citaton Type |
Other |
Standard Cited |
19100157 G04 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.157(g)(4): Employees who have been designated to use fire fighting equipment as a part of the emergency action plan were not provided training in the use of appropriate equipment upon initial assignment and at least annually thereafter: a) For the shop location, as observed on or about 10/20/2016, employees designated to use fire extinguishers for small/incipient fires were not provided with annual fire extinguisher training. |
|
Citation ID |
02005 |
Citaton Type |
Other |
Standard Cited |
19100178 L04 III |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years: a) For the shop location, as observed on or about 10/25/2016, a Yale forklift was used, and employees who operated the forklift had not been trained/evaluated on forklifts in the last three years. |
|
Citation ID |
02006 |
Citaton Type |
Other |
Standard Cited |
19100178 L06 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-28 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
4 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): a) For the shop location, as observed on or about 10/25/2016, employees operated sit-down propane forklifts, and certification records of employees' training and evaluation was not available. |
|
Citation ID |
02007 |
Citaton Type |
Other |
Standard Cited |
19100180 D06 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
4 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.180(d)(6): Monthly, dated and signed inspection records and reports for truck crane(s) were not provided for critical items such as (but not limited to) brakes, crane hooks and ropes: a) For the truck cranes used, as observed on or about 10/25/2016, monthly truck crane inspections were not documented. |
|
Citation ID |
02008 |
Citaton Type |
Other |
Standard Cited |
19100303 E01 II |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(e)(1)(ii): Markings were not provided on electrical equipment for voltage, current, wattage and other ratings as necessary. a) For the areas inside the shop where electrical panels were located, as observed on or about 10/20/2016, the panels were not marked with electrical ratings. b) For the area outside the shop on the exterior wall where electric panels were located, as observed on or about 10/20/2016, the panels were not marked with electrical ratings. |
|
Citation ID |
02009 |
Citaton Type |
Other |
Standard Cited |
19101200 E01 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-28 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(e)(1): Employer had not developed or implemented a written hazard communication program included the requirements outlined in 29 CFR 1910.1200(e)(1)(i) and (e)(1)(ii): a) For chemicals at the shop location, as observed on or about 10/20/2016, a written hazard communication program was not available. Chemicals present included, but were not limited to, paints, oils, brake cleaner, purple power cleaner/degreaser, and gasoline. |
|
Citation ID |
02010 |
Citaton Type |
Other |
Standard Cited |
19101200 F10 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-13 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(10): The employer did not ensure that workplace labels or other forms of warnings were legible, in English and prominently displayed on the container or readily available in the work area throughout each work shift: a) For the shop location, as observed on or about 10/20/2016, the 55 gallon container of Purple Power cleaner/degreaser was not labeled to indicate what its contents were. b) For the exterior wall of the shop, as observed on or about 10/20/2016, a 550 gallon drum of motor oil was not labeled to indicate what its contents were. |
|
Citation ID |
02011 |
Citaton Type |
Other |
Standard Cited |
19101200 G08 |
Issuance Date |
2016-12-01 |
Abatement Due Date |
2016-12-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-12-07 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(g)(8): The employer did not maintain copies of the required safety data sheets for each hazardous chemical in the workplace: a) For the shop location, as observed on or about 10/20/2016, safety data sheets were missing for hazardous chemicals such as, but not limited to, Prime Blend Automotive Spray Paint and Project Source Spray Paint #282255. |
|