Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2015-01-15
|
Emphasis |
L: EISAOF, L: EISAX, L: FORKLIFT
|
Case Closed |
2015-02-26
|
Related Activity
Type |
Complaint |
Activity Nr |
931446 |
Safety |
Yes |
Health |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100151 C |
Issuance Date |
2015-02-10 |
Abatement Due Date |
2015-03-09 |
Current Penalty |
960.0 |
Initial Penalty |
1600.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Ink Room - No eyewash was provided where cleaners containing alkalines were used, on or about January 15, 2015. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100215 A04 |
Issuance Date |
2015-02-10 |
Current Penalty |
960.0 |
Initial Penalty |
1600.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: a) Cut Room - Central Machinery 6" bench grinder, number 37822, work rest on the right side was 5/16" from the wheel, on or about January 15, 2015. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100215 B09 |
Issuance Date |
2015-02-10 |
Abatement Due Date |
2015-02-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) Cut Room - Central Machinery 6" bench grinder, number 37822, was missing the tongue guard, on or about January 15, 2015. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19101200 E01 |
Issuance Date |
2015-02-10 |
Abatement Due Date |
2015-03-09 |
Current Penalty |
720.0 |
Initial Penalty |
1200.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
25 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: a) Facility-wide - There was no written hazard communication program in place, on or about January 15, 2015. Chemicals used included 2-methoxymethylethoxy propanol, propylene glycol, ethylene glycol, and hydrocracked and hydrotreated paraffinic oils. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19101200 F05 |
Issuance Date |
2015-02-10 |
Abatement Due Date |
2015-02-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(5): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged, or marked with the identity and appropriate hazard warnings regarding the chemicals contained therein: a) Ink Room - Secondary bottles of chemicals, including but not limited to, inks, cleaning solutions and vacuum pump oil were not provided with labels, on or about January 15, 2015. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100303 G01 |
Issuance Date |
2015-02-10 |
Abatement Due Date |
2015-02-17 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-02-24 |
Nr Instances |
1 |
Nr Exposed |
25 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Pre-treat Room - There were containers on the floor in front of the electrical panels, on or about January 15, 2015. |
|
|