341067296
|
0420600
|
2015-11-19
|
1540 12TH STREET EAST, PALMETTO, FL, 34221
|
|
Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2015-11-19
|
Emphasis |
N: AMPUTATE, P: AMPUTATE
|
Case Closed |
2016-04-28
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100023 C01 |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
1200.0 |
Initial Penalty |
2000.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:Note: Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard. a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. Employees were exposed to a fall hazard above the office. Fall height was approximately 10 feet. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100157 C04 |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
720.0 |
Initial Penalty |
1200.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. Employees were exposed to a fire hazard in that a fire extinguisher located behind the ovens was not fully charged and in an operable condition. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100242 B |
Issuance Date |
2016-04-01 |
Current Penalty |
1680.0 |
Initial Penalty |
2800.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 psi.: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. Employees were using compressed air to clean material and clothing that was at a pressure greater than 30 p.s.i. Air pressure that was used was approximately 114 p.s.i. |
|
Citation ID |
01004A |
Citaton Type |
Serious |
Standard Cited |
19100263 E01 I |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
1680.0 |
Initial Penalty |
2800.0 |
Final Order |
2016-04-22 |
Nr Instances |
2 |
Nr Exposed |
2 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.263(e)(1)(i): Mixers with external power application shall have all belts, chains, gears, pulleys, sprockets, clutches, and other moving parts completely enclosed. a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. Employees were using 2 vertical mixers that did not have the moving hook parts enclosed. |
|
Citation ID |
01004B |
Citaton Type |
Serious |
Standard Cited |
19100263 C03 |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.263(c)(3): Sprocket(s) and V-belt drive(s) of bakery machinery located within reach from platform(s) or passageway(s) or located within 8 feet 6 inches from the floor were not completely enclosed: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. Employees were using the bread bagging machine that did not have a cover or guard over the drive gear sprocket and chain. |
|
Citation ID |
01005A |
Citaton Type |
Serious |
Standard Cited |
19100303 G02 I |
Issuance Date |
2016-04-01 |
Current Penalty |
1200.0 |
Initial Penalty |
2000.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. At the bread molder the electrical box was missing the cover exposing energized conductors. |
|
Citation ID |
01005B |
Citaton Type |
Serious |
Standard Cited |
19100303 B07 I |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-04-22 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. a) At the main power panel that housed the main breakers for the building outlets and lights, one of the breakers was removed and no cover was installed in its place. b) At the bread mixing machine main operating panel the 2 speed timers were missing and the openings were not covered. |
|
Citation ID |
01006 |
Citaton Type |
Serious |
Standard Cited |
19100303 G01 |
Issuance Date |
2016-04-01 |
Current Penalty |
1440.0 |
Initial Penalty |
2400.0 |
Final Order |
2016-04-22 |
Nr Instances |
2 |
Nr Exposed |
14 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. a)The main electrical panels for the building did not have sufficient access due to oven racks being stored directly in front of the panel boards. The 4 foot long oven racks were stored approximately 12 inches from the face of the panel board. b) The main oven electrical panels did not have sufficient access due to bread boards and molds being stored directly in front of the panel boards. The bread boards and molds were approximately touching the face of the panel board. |
|
Citation ID |
01007 |
Citaton Type |
Serious |
Standard Cited |
19100305 A01 I |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
1200.0 |
Initial Penalty |
2000.0 |
Final Order |
2016-04-22 |
Nr Instances |
1 |
Nr Exposed |
12 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not connected to all boxes, fittings, and cabinets to provide effective electrical continuity: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. At the main electrical panel the metal raceway was not connected to the panel. The raceway was approximately 6 inches from the top of the panel box. The electrical conductors were holding the raceway in place. The raceway was feeding an energized 120 volt outlet. |
|
Citation ID |
01008 |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2016-04-01 |
Abatement Due Date |
2016-04-13 |
Current Penalty |
1200.0 |
Initial Penalty |
2000.0 |
Final Order |
2016-04-22 |
Nr Instances |
2 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) For employees working at 1540 12th Street East located in Palmetto, as observed on or about 19 November, 2015. The electrical cord that supplied power to the moveable bread forming machine did not have strain relief at the plug and at the box connection. |
|
|
14073043
|
0420600
|
1980-04-16
|
2730 KNIGHTS STATION ROAD, Lakeland, FL, 33802
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1980-04-16
|
Case Closed |
1980-04-29
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19100023 C01 |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-26 |
Nr Instances |
1 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100134 B01 |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-26 |
Nr Instances |
3 |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100134 F02 IV |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-21 |
Nr Instances |
3 |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100157 A01 |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-21 |
Nr Instances |
1 |
|
Citation ID |
01005 |
Citaton Type |
Other |
Standard Cited |
19100309 A 025051 |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-21 |
Nr Instances |
1 |
|
Citation ID |
01006 |
Citaton Type |
Other |
Standard Cited |
19100309 A 040010 |
Issuance Date |
1980-04-18 |
Abatement Due Date |
1980-04-21 |
Nr Instances |
1 |
|
|
14018394
|
0420600
|
1979-03-14
|
2730 KNIGHTS STATION ROAD, Lakeland, FL, 33801
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1979-03-14
|
Case Closed |
1979-03-21
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19100219 C04 I |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100219 D01 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100309 A 011014 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100309 A 025051 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01005 |
Citaton Type |
Other |
Standard Cited |
19100309 A 040004 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01006 |
Citaton Type |
Other |
Standard Cited |
19100309 B 011016 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01007 |
Citaton Type |
Other |
Standard Cited |
19100309 B 037018 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
Citation ID |
01008 |
Citaton Type |
Other |
Standard Cited |
19100309 B 037304 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
6 |
|
Citation ID |
01009 |
Citaton Type |
Other |
Standard Cited |
19100309 B 040001 |
Issuance Date |
1979-03-16 |
Abatement Due Date |
1979-03-23 |
Nr Instances |
1 |
|
|
14030225
|
0420600
|
1978-02-10
|
2730 KNIGHTS STATION ROAD, Lakeland, FL, 33801
|
|
Inspection Type |
FollowUp
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1978-02-10
|
Case Closed |
1984-03-10
|
|
14030134
|
0420600
|
1978-01-20
|
2730 KNIGHTS STATION ROAD, Lakeland, FL, 33801
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1978-01-20
|
Case Closed |
1978-02-17
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100212 A01 |
Issuance Date |
1978-01-24 |
Abatement Due Date |
1978-02-01 |
Current Penalty |
270.0 |
Initial Penalty |
270.0 |
Nr Instances |
1 |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100151 C |
Issuance Date |
1978-01-24 |
Abatement Due Date |
1978-02-01 |
Nr Instances |
4 |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100309 A 040004 |
Issuance Date |
1978-01-24 |
Abatement Due Date |
1978-01-27 |
Nr Instances |
1 |
|
|
14078414
|
0420600
|
1977-02-24
|
1900 GRIFFIN ROAD, Lakeland, FL, 33803
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1977-02-24
|
Case Closed |
1977-03-03
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19100106 G03 IVD |
Issuance Date |
1977-02-28 |
Abatement Due Date |
1977-03-16 |
Nr Instances |
1 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100178 K02 |
Issuance Date |
1977-02-28 |
Abatement Due Date |
1977-03-03 |
Nr Instances |
1 |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100215 A04 |
Issuance Date |
1977-02-28 |
Abatement Due Date |
1977-03-03 |
Nr Instances |
1 |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100309 A 025045 |
Issuance Date |
1977-02-28 |
Abatement Due Date |
1977-03-03 |
Nr Instances |
1 |
|
|