Search icon

GP CELLULOSE, LLC - Florida Company Profile

Company Details

Entity Name: GP CELLULOSE, LLC
Jurisdiction: FLORIDA
Filing Type: Foreign Limited Liability Co.
Status: Active

The business entity is active. This status indicates that the business is currently operating and compliant with state regulations, suggesting a lower risk profile for lenders and potentially better creditworthiness.

Date Filed: 03 Apr 2014 (11 years ago)
Last Event: LC STMNT OF RA/RO CHG
Event Date Filed: 22 Jul 2021 (4 years ago)
Document Number: M14000002320
FEI/EIN Number 90-0139554

Federal Employer Identification (FEI) Number assigned by the IRS.

Address: 133 Peachtree St NE, Atlanta, GA, 30303, US
Mail Address: 133 Peachtree St NE, Atlanta, GA, 30303, US
Place of Formation: DELAWARE

Key Officers & Management

Name Role Address
Darland Tye G. Manager 133 Peachtree St NE, Atlanta, GA, 30303
Abdallah Munir L. Manager 133 Peachtree St NE, Atlanta, GA, 30303
Boushka Patrick J Manager 133 Peachtree St NE, Atlanta, GA, 30303
UNITED AGENT GROUP INC. Agent -

Events

Event Type Filed Date Value Description
CHANGE OF PRINCIPAL ADDRESS 2023-04-12 133 Peachtree St NE, Atlanta, GA 30303 -
CHANGE OF MAILING ADDRESS 2023-04-12 133 Peachtree St NE, Atlanta, GA 30303 -
REGISTERED AGENT NAME CHANGED 2023-04-12 UNITED AGENT GROUP INC. -
LC STMNT OF RA/RO CHG 2021-07-22 - -
REGISTERED AGENT ADDRESS CHANGED 2021-07-22 801 US HIGHWAY 1, NORTH PALM BEACH, FL 33408 -

Debts

Document Number Status Case Number Name of Court Date of Entry Expiration Date Amount Due Plaintiff
J21000216410 TERMINATED 1000000886766 TAYLOR 2021-04-27 2041-05-05 $ 2,542.59 STATE OF FLORIDA, DEPARTMENT OF REVENUE, OUT OF STATE COLLECTIONS UNIT, 1415 W US HIGHWAY 90 STE 115, LAKE CITY FL320556156

Documents

Name Date
ANNUAL REPORT 2024-04-24
ANNUAL REPORT 2023-04-12
ANNUAL REPORT 2022-04-26
CORLCRACHG 2021-07-22
ANNUAL REPORT 2021-04-24
ANNUAL REPORT 2020-05-11
ANNUAL REPORT 2019-03-19
ANNUAL REPORT 2018-04-24
ANNUAL REPORT 2017-04-06
ANNUAL REPORT 2016-04-09

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
339794000 0419700 2014-05-30 ONE BUCKEYE DR., PERRY, FL, 32347
Inspection Type Referral
Scope Complete
Safety/Health Safety
Close Conference 2014-06-19
Emphasis N: CHEMNEP
Case Closed 2014-11-26

Related Activity

Type Referral
Activity Nr 891547
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19100119 E03 I
Issuance Date 2014-10-15
Current Penalty 5115.0
Initial Penalty 5500.0
Final Order 2014-11-07
Nr Instances 1
Nr Exposed 11
Related Event Code (REC) Referral
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.119(e)(3)(i): The Process Hazard Analysis did not address the hazards of the process: a. On or about May 28, 2014, in the chlorine dioxide R-8 plant, the Process Hazard Analysis did not address the hazard of deflagration due to contamination of the supply or emergency water sources, or the measures to control those hazards.
Citation ID 01002
Citaton Type Other
Standard Cited 19100119 J04 III
Issuance Date 2014-10-15
Current Penalty 0.0
Initial Penalty 5500.0
Final Order 2014-11-07
Nr Instances 2
Nr Exposed 11
Related Event Code (REC) Referral
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment to maintain its mechanical integrity, was not consistent with applicable manufacturer's recommendations and good engineering practices, or more frequently determined to be necessary by prior operating experience: a. On or about May 28, 2014, at the chlorine dioxide system, the annual external piping inspection had not been conducted for over 20 months, exposing employees to the potential hazard of chlorine dioxide exposure from deteriorating piping system components. b. On or about May 28, 2014, at the chlorine dioxide ERCO R-8 generator, the deflagration vent cover and vent duct interior had not received an annual inspection, exposing employees to the hazard of a potential chlorine dioxide generator vessel rupture.
Citation ID 01003
Citaton Type Serious
Standard Cited 19100119 J06 III
Issuance Date 2014-10-15
Current Penalty 4290.0
Initial Penalty 4675.0
Final Order 2014-11-07
Nr Instances 1
Nr Exposed 8
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.119(j)(6)(iii): The employer did not assure that maintenance materials, spare parts, and equipment were suitable for the process application for which they were used: a. On or about May 28, 2014, chlorine dioxide deflagration vent rain hat did not have a fly-off tether, exposing employees to the hazard of being struck by the metal disk during a deflagration event.