Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2024-02-23
|
Emphasis |
L: FORKLIFT
|
Case Closed |
2024-03-28
|
Related Activity
Type |
Complaint |
Activity Nr |
2131649 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100022 A01 |
Issuance Date |
2024-03-07 |
Current Penalty |
2903.4 |
Initial Penalty |
4839.0 |
Final Order |
2024-03-26 |
Nr Instances |
1 |
Nr Exposed |
35 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. a) For the production floor, on or about 02/23/2024, the employer exposed employees to trip hazards, in that, extension cords, pallets and other items were left in walking areas accessed by employees. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100303 G02 I |
Issuance Date |
2024-03-07 |
Current Penalty |
3871.8 |
Initial Penalty |
6453.0 |
Final Order |
2024-03-26 |
Nr Instances |
1 |
Nr Exposed |
30 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) For the electrical control cabinet by the outline machines, on or about 02/23/2024, the employer exposed employees to electrical shock hazards, in that, 120 VAC electrical parts were not protected by an approved cabinet since the cabinet door was left unlocked and open, exposing live parts. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2024-03-07 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-03-26 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) For the 120/240VAC subpanel 2 on the production floor, on or about 02/23/2024, the employer exposed employees to electrical shock hazards, in that, blank covers were not installed over missing circuit break slots at gaps measured to be approximately 1-2 inches. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2024-03-07 |
Current Penalty |
2903.4 |
Initial Penalty |
4839.0 |
Final Order |
2024-03-26 |
Nr Instances |
1 |
Nr Exposed |
30 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) For the production floor, on or about 02/23/2024, the employer exposed employees to electrical shock/burn hazards, in that, an extension cord used to power a floor fan had damaged insulation at its plug resulting in a lack of strain relief for the inner cord conductors. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100303 F02 |
Issuance Date |
2024-03-07 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-03-26 |
Nr Instances |
1 |
Nr Exposed |
30 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) For the production floor, on or about 02/23/2024, the employer exposed employees to potential shock hazards, in that, multiple breaker panel cabinets throughout the shop were not legibly labeled at their circuit breakers. |
|
|