Search icon

MOTOR CITY ELECTRIC UTILITIES COMPANY - Florida Company Profile

Company Details

Entity Name: MOTOR CITY ELECTRIC UTILITIES COMPANY
Jurisdiction: FLORIDA
Filing Type: Foreign Profit
Status: Active

The business entity is active. This status indicates that the business is currently operating and compliant with state regulations, suggesting a lower risk profile for lenders and potentially better creditworthiness.

Date Filed: 13 Dec 2007 (17 years ago)
Document Number: F07000006075
FEI/EIN Number 382511645

Federal Employer Identification (FEI) Number assigned by the IRS.

Address: 9440 GRINNELL, DETROIT, MI, 48213
Mail Address: 9440 GRINNELL, DETROIT, MI, 48213
Place of Formation: MICHIGAN

Key Officers & Management

Name Role Address
WIECZOREK DALE Chairman 9440 GRINNELL, DETROIT, MI, 48213
Volkman, Jr. David R. President 9440 GRINNELL, DETROIT, MI, 48213
HODGINS DENISE Executive Vice President 9440 GRINNELL, DETROIT, MI, 48213
LEVINE STUART J Agent 601 BAYSHORE BLVD., TAMPA, FL, 33606

Documents

Name Date
ANNUAL REPORT 2025-01-08
ANNUAL REPORT 2024-01-18
ANNUAL REPORT 2023-01-27
ANNUAL REPORT 2022-03-02
ANNUAL REPORT 2021-01-15
ANNUAL REPORT 2020-01-03
ANNUAL REPORT 2019-01-10
ANNUAL REPORT 2018-01-05
ANNUAL REPORT 2017-01-13
ANNUAL REPORT 2016-01-20

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
340879063 0418800 2015-08-27 1023 S. DEERFIELD AVENUE, DEERFIELD BEACH, FL, 33441
Inspection Type Referral
Scope Partial
Safety/Health Safety
Close Conference 2015-09-02
Case Closed 2016-03-29

Related Activity

Type Referral
Activity Nr 1014457
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Other
Standard Cited 19100026 C03 I
Issuance Date 2016-01-22
Current Penalty 7000.0
Initial Penalty 7000.0
Final Order 2016-03-22
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Referral
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.26(c)(3)(i): The angle of the ladder was not proper in that distance from the base to the vertical wall was not equal to one-fourth the working length of the ladder: On or about August 26, 2015, at the above addressed jobsite, an employee was using an aluminum/fiberglass extension ladder to change-out three electrical switches at a sub-station, wherein the ladder was not set-up at the proper angle (4:1 Ratio, 25 Percent or 14 Degrees); and wherein the employee on the ladder was working within close proximity to the energized adjacent overhead lines; therefore exposing the employee to fall and electrical hazards.
Citation ID 01002A
Citaton Type Serious
Standard Cited 19100269 L03 III A
Issuance Date 2016-01-22
Current Penalty 4900.0
Initial Penalty 7000.0
Final Order 2016-03-22
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.269(l)(3)(iii)(A): The employee was not insulated from the energized part: On or about August 26, 2015, at the above addressed jobsite, an employee was using an aluminum extension ladder to change-out three electrical switches at a sub-station, without the use of rubber protective gloves and sleeves (PPE); and wherein the employee on the ladder made electrical contact with the adjacent overhead energized lines, which resulted in the serious injury/hospitalization of the employee, and the exposure to electrical hazard to the other two employees.
Citation ID 01002B
Citaton Type Serious
Standard Cited 19100269 L03 III B
Issuance Date 2016-01-22
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2016-03-22
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Referral
Gravity 10
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.269(l)(3)(iii)(B): The energized part was not insulated from the employee and from any other conductive object at a different potential: On or about August 26, 2015, at the above addressed jobsite, an employee was using an aluminum extension ladder to change-out three electrical switches at a sub-station, without first guarding and/or insulating the adjacent overhead energized lines; and wherein the employee on the ladder made electrical contact with the adjacent overhead energized lines, which resulted in the serious injury/hospitalization of the employee, and the exposure to electrical hazard to the other two employees.