341057610
|
0420600
|
2015-11-16
|
2512 N 15TH ST, TAMPA, FL, 33605
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2016-02-02
|
Case Closed |
2016-04-13
|
Related Activity
Type |
Complaint |
Activity Nr |
1036960 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100303 G01 |
Issuance Date |
2016-02-08 |
Abatement Due Date |
2016-02-19 |
Current Penalty |
1260.0 |
Initial Penalty |
2100.0 |
Final Order |
2016-02-18 |
Nr Instances |
2 |
Nr Exposed |
24 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: At 2512 N 15th Street Tampa, Florida, as observed on or about 11/16/2015. a) access to electrical panel at the pastry department was obstructed by a table and a shelf b) access to electrical panels at the oven areas were obstructed by shelves, trash can and baking equipment. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100303 F02 |
Issuance Date |
2016-02-08 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-02-18 |
Nr Instances |
1 |
Nr Exposed |
24 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident a) For electrical panel located at the pastry department located at 2512 N 15th Street Tampa, Florida, as observed on or about 11/16/2015. |
|
|
334405131
|
0420600
|
2012-05-15
|
2512 N. 15TH ST., TAMPA, FL, 33605
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2012-05-15
|
Emphasis |
N: SSTARG11, L: EISAOF
|
Case Closed |
2012-10-10
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
5A0001 |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-11-22 |
Current Penalty |
1800.0 |
Initial Penalty |
3500.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
30 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of being struck by fragments of Polyvinyl Chloride (PVC) Plastic Pipe in the event that the PVC plastic pipe ruptures: (a) for employees using compressed air located in the work areas at 2512 N. 15th St. Tampa, Fl , as observed on or about 5/17/2012. The facility used PVC Plastic Piping in exposed above ground locations to distribute compressed air throughout the facility for cleaning the floor and baking pans. The piping was connected to a BelAire 5-HP 60-Gallon Dual-Voltage Two-Stage, (Model #216V, Serial #HOP263011) 165 psi compressor operating at 120 psi. The use of PVC plastic pipe in exposed above ground locations is not recommended by the Plastic Pipe Institute, and such use is prohibited by ANSI/ASME B31.8-1986, Gas Transmission and Distribution Piping Systems Standard. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100303 B02 |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-09-14 |
Current Penalty |
1100.0 |
Initial Penalty |
2100.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
5 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) At the site - in the bakery a metal outlet box on the Peerless Mixer, S.N. 68006 was not secured or mounted to the wall or other surface as intended by the manufacturer, on or about 5/17/12. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 II |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-09-14 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) At the site - in the bakery on the Peerless Mixer S.N. 68006, the unused opening "knockouts" on a metal junction box were not closed, on or about 5/17/12. (b) At the site - in the bakery a breaker panel box had an unused opening, on or about 5/17/12. |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19100305 B02 I |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-09-14 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) At the site - near the back entrance to the bakery light switch was missing a cover, on or about 5/17/12 |
|
Citation ID |
01002D |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-09-14 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) At the site - In the bakery the insulation of the Scale-O-Matic machine was pulled back from the plug exposing the interior creating a possible electrical shock hazard, on or before 5/1/2012. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19040004 A |
Issuance Date |
2012-09-07 |
Abatement Due Date |
2012-10-22 |
Current Penalty |
400.0 |
Initial Penalty |
700.0 |
Final Order |
2012-09-19 |
Nr Instances |
1 |
Nr Exposed |
42 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1904.4(a): The employer did not record each work-related fatality, injury or illness case that resulted in the general recording criteria on the OSHA Form 300 or equivalent. (a) At the site - the employer did not record and maintain and OSHA 300 or its equivalent of work-related injuries or illness cases in accordance with this standard, on or about 05/17/2012. |
|
|
13994785
|
0420600
|
1982-08-16
|
3416 N 15TH ST, Tampa, FL, 33605
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1982-08-16
|
Case Closed |
1982-08-27
|
Violation Items
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100157 C04 |
Issuance Date |
1982-08-19 |
Abatement Due Date |
1982-08-27 |
Nr Instances |
2 |
|
|
14053425
|
0420600
|
1980-08-05
|
3416 NORTH 15TH STREET, Tampa, FL, 33605
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1980-08-05
|
Case Closed |
1984-03-10
|
|
13978614
|
0420600
|
1979-05-10
|
3416 N 15 STREET, Tampa, FL, 33605
|
|
Inspection Type |
FollowUp
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1979-05-10
|
Case Closed |
1984-03-10
|
|
14018626
|
0420600
|
1979-04-20
|
3416 N 15 ST, Tampa, FL, 33605
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1979-04-20
|
Case Closed |
1979-05-14
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100212 A01 |
Issuance Date |
1979-04-23 |
Abatement Due Date |
1979-05-09 |
Current Penalty |
150.0 |
Initial Penalty |
150.0 |
Nr Instances |
1 |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100309 A 011022 |
Issuance Date |
1979-04-23 |
Abatement Due Date |
1979-04-30 |
Nr Instances |
18 |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100309 B 040001 |
Issuance Date |
1979-04-23 |
Abatement Due Date |
1979-04-30 |
Nr Instances |
1 |
|
|
14065908
|
0420600
|
1976-11-03
|
3416 NORTH 15TH STREET, Tampa, FL, 33605
|
|
Inspection Type |
Planned
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
1976-11-03
|
Case Closed |
1976-11-23
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19030002 A01 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
1 |
|
Citation ID |
01002 |
Citaton Type |
Other |
Standard Cited |
19100023 C01 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-29 |
Nr Instances |
1 |
|
Citation ID |
01003 |
Citaton Type |
Other |
Standard Cited |
19100037 Q01 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
1 |
|
Citation ID |
01004 |
Citaton Type |
Other |
Standard Cited |
19100219 F03 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
1 |
|
Citation ID |
01005 |
Citaton Type |
Other |
Standard Cited |
19100309 A 025045 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
2 |
|
Citation ID |
01006 |
Citaton Type |
Other |
Standard Cited |
19100309 A 040010 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
1 |
|
Citation ID |
01007 |
Citaton Type |
Other |
Standard Cited |
19100309 B 037015 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
1 |
|
Citation ID |
01008 |
Citaton Type |
Other |
Standard Cited |
19100309 B 037304 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
3 |
|
Citation ID |
01009 |
Citaton Type |
Other |
Standard Cited |
19100309 B 041052 |
Issuance Date |
1976-11-05 |
Abatement Due Date |
1976-11-22 |
Nr Instances |
3 |
|
|